EJX120A Differential Pressure Transmitter |
| E Capsule |
| Range |
-1 to 1 kPa
(-4 to 4 inH2O) |
| Span |
0.025 to 1 kPa
(0.1 to 4 inH2O) |
| Accuracy |
±0.09% |
| Degrees of protection |
IP67, NEMA 4X, and JIS C0920 immersion proof |
| Certificates |
FM, CENELEC ATEX, CSA, IECEx |
| Output |
4 to 20 mA DC or FOUNDATION™ fieldbus, 2-wire system with digital communication |
| Supply voltage |
BRAIN and HART:10.5 to 42 V DC (10.5 to 30 V DC for Intrinsically safe type) Fieldbus:9 to 32 V DC (9 to 24 V DC for Entity and 9 to 17.5 V DC for FISCO) |
| Ambient temperature |
-25 to 80 deg C (-13 to 176 deg F) (general use type) |
| Process temperature |
-25 to 80 deg C (-13 to 176 deg F) (general use type) |
| Maximum working pressure |
50 kPa
(7.25 psi) |
| Mounting |
2-inch pipe mounting |
| Wetted parts material |
Capsule |
316L SST(Diaphragm material is Hastelloy C-276) |
| Cover flange |
ASTM CF-8M |
| Housing |
Cast aluminum alloy or ASTM CF-8M stainless steel (optional) |