EJX118A Diaphragm Sealed Differential Pressure Transmitter |
| M Capsule |
H Capsule |
| Range |
-100 to 100 kPa
(-400 to 400 inH2O) |
-500 to 500 kPa
(-2000 to 2000 inH2O) |
| Span |
2 to 100 kPa
(8 to 400 inH2O) |
10 to 500 kPa
(40 to 2000 inH2O) |
| Accuracy |
±0.15% |
±0.15% |
| Degrees of protection |
IP67, NEMA 4X, and JIS C0920 immersion proof |
| Certificates |
FM, CENELEC ATEX, CSA, IECEx |
| Output |
4 to 20 mA DC or FOUNDATION™ fieldbus, 2-wire system with digital communication |
| Supply voltage |
BRAIN and HART:10.5 to 42 V DC (10.5 to 30 V DC for Intrinsically safe type) Fieldbus:9 to 32 V DC (9 to 24 V DC for Entity and 9 to 17.5 V DC for FISCO) |
| Ambient temperature |
-40 to 60 deg C (-40 to 140 deg F) (general use type)
-30 to 60 deg C (-22 to 140 deg F) (with integral indicator) It must be within the fill fluid operating temperature range. |
| Process temperature |
-50 to 310 deg C (-58 to 590 deg F)
It must be within the fill fluid operating temperature range. |
Maximum working
pressure |
Flange rating pressure |
| Mounting |
Transmitter: 2-inch pipe mounting
Diaphragm seals: flange mounting |
| Process flange size |
| Flush type: |
3-inch (80 mm), 2-inch (50 mm),
1 1/2-inch (40 mm) |
| Extended type: |
4-inch (100 mm), 3-inch (80 mm) |
Combination type: |
4-inch (100 mm) for extended high side,
3-inch (80 mm) for flush low side |
|
| Diaphragm material |
SUS316L, Hastelloy C-276, Tantalum, Titanium |
| Process flange material |
S25C, SUS304, SUS316 |
| Housing |
Cast aluminum alloy or ASTM CF-8M stainless steel (optional) |